StatiVolt ® Inverter UPS Systems

StatiVolt ® Inverter UPS Systems

StatiVolt ® inverter UPS systems provide regulated, filtered and conditioned sine-wave AC power from a DC power input. Each inverter UPS includes one or more parallel StatiVolt ® inverters combined with a no-break auto transfer to an alternate source, and a no-break maintenance bypass switch. An optional bypass isolation / step-down transformer is available. These systems are natural convection cooled, have a 30 year design life, and are fully CSA certified, including the transfer.


Output
kVA
DC Input kW (1Ø)
24 V 48 V 125 V 250 V
0.6 1.8 1 1 0.9 0.9
1.2 3.6 1.7 1.7 1.6 1.5
2.0 6.0 2.7 2.6 2.5 2.4
3.0 9.0 4.1 3.8 3.7 3.5
4.0 12.0 5.3 5.1 4.8 4.5
5.0 15.0 6.7 6.3 6 5.6
6.0 18.0   7.5 7.1 6.7
7.5 22.5   9.4 8.8 8.3
10.0 30.0   13 12 11
12.5 37.5   16 15 14
15.0 45.0   19 18 17
20.0 60.0     24 22
25.0 75.0     29 28
30.0 90.0     35 33
40.0 120.0     47 44
50.0 150.0     59 56
60.0 180.0     71 67

Reliability by Design

  • Pure Sine-Wave AC Power
  • Low Frequency, Soft-Switching
  • Natural Convection Cooled
  • 30 Year Design Life


Low DC Input Voltage

  • 24, 48, 125, 250 V DC Nominal
  • Battery-Only Start-Up Capability


Protection

  • In, Out, Bypass Circuit Breakers
  • Fail-Safe Output Current Limiting
  • Transformer Isolation
  • Fail-Safe Output V Control
  • Inherent Surge Rejection
  • Inherent AC Fault Limiting

Versatile Functions & Options

  • DC Input Low V Shutdown
  • Dual AC Output Voltages
  • Static Switch Initiated Transfer
  • Bypass Transformer
  • Special Utility Options
  • 2 year full, 5 year major parts
  • Fully field serviceable
  • 20 year parts availability



TOP